CC6367
CC6367
- ATEX/IECEx certified for hazardous locations Class I, Zone 2 environments
- CC6367PHL Rated Cooling: 6,389 Watts mounted to an uninsulated 72" x 36" x 24" Cabinet with 1 GMP of water at 20°C, 40°C ambient air and 60°C cabinet air temperature
- Designed for surface mounting on outside of cabinet
- Housing is Stainless Steel (TYPE 316 14 GAUGE)
- External water inlet and outlet connections
- Equipped with mounting gasket to maintain airtight seal
- Available with AC (115 & 230V) and DC (12, 24 & 48V)
- Vertical mounting only
- Coolant water pressure: Pressure tested to 100psi. Safe working pressure is 60 psi.
- Recommended coolant water flow rate (gallons per minute): 1GPM
- ATEX/IECEx Standards: 60079-0, 6th Ed. + Corr. 1:2012 + Corr. 2:2013, IEC 60079-15, 4th Ed., CENELEC EN 60079-0:2012 + A11:2013 and CENELEC EN 60079-15:2010
DETAILS
Dimensions-Inches | ||||||||
---|---|---|---|---|---|---|---|---|
Model | Weight (lbs) | Rating (Watts) @ 20 °C ▲T | Rating (BTU/hr) @ 20 °C ▲T | Amps Current Draw at 115 V | Fan Size | Height | Width | Depth |
CC6367PHL | 52 | 6,389 | 21,800 | 0.9 | 3 x 6" | 30.3 | 14 | 8 | 159.7 Watts /°C ∆T based on average internal cabinet temperature |
CERTIFICATIONS