CC6365

CC6365

  • UL Listed for TYPE 4X environments, Hazard Location Class 1/ Div 2
  • CC6365PHL Rated Cooling: 6,389 Watts mounted to an uninsulated 72" x 36" x 24" cabinet with 1GPM of water at 20°C, 40°C ambient air and 60°C cabinet air temperature (Temp Code T4)
  • Designed for surface mounting on the outside of cabinet
  • Housing is Stainless Steel (TYPE 316)
  • External water inlet and outlet connections
  • Equipped with mounting gasket to maintain the TYE 4X integrity of your cabinet
  • Pressure tested to insure liquid tight seal
  • Internal 6-ft power cord
  • Available with DC and AC (12VDC, 24VDC, 48VDC, 115VAC & 230VAC) Designation xxx indicates voltage
  • Vertical mounting (as shown) only
  • Coolant water pressure: Pressure tested to 100 psi. Safe working pressure is 60 psi.
  • Recommended coolant water flow rate (gallons per minute): 1GPM

DETAILS

Dimensions-Inches
Model Weight (lbs) Rating (Watts) @ 20 °C ▲T Rating (BTU/hr) @ 20 °C ▲T Amps Current Draw at 115 V Fan Size Height Width Depth
CC6365PHL 32 6,389 21,800 21,800 3 x 6" 29 13.8 7.94
159.7 Watts /°C ∆T based on average internal cabinet temperature