CC3067

CC3067

  • ATEX/IECEx certified for hazardous locations Class I, Zone 2 environments
  • CC3067PHL Rated Cooling: 2,725 Watts mounted to an uninsulated 72" x 36" x 24" Cabinet with 1 GPM of water at 20°C, 40°C ambient air and 60°C cabinet air temperature
  • Designed for surface mounting on outide of cabinet
  • Housing is Stainless Steel (TYPE 316 14 GAUGE)
  • External water inlet and outlet connections
  • Equipped with mounting gasket to maintain airtight seal
  • Pressure tested to assure watertight seal
  • Available with AC (115 & 230V) and DC (12, 24 & 48V)
  • Vertical mounting only
  • Coolant water pressure: Pressure tested to 100psi. Safe working pressure is 60 psi
  • Recommended water flow rate (gallons per minute): 1GPM
  • ATEX/IECEx Standards: 60079-0. 6th Ed. + Corr. 1:2012 + Corr. 2:2013, IEC 60079-15, 4th Ed., CENELEC EN 60079-0:2012 + A11:2013 and CENELEC EN 60079-15:2010

DETAILS

Dimensions-Inches
Model Weight (lbs) Rating (Watts) @ 20 °C ▲T Rating (BTU/hr) @ 20 °C ▲T Amps Current Draw at 115 V Fan Size Height Width Depth
CC3067PHL 25 2,725 9,300 0.3 1 x 6" 33.8 9.25 4
68.8 Watts /°C ∆T based on average internal cabinet temperature

CERTIFICATIONS

GET A QUOTE FOR YOUR HEAT EXCHANGER