CC2065
CC2065
- UL Listed for TYPE 4X environments, Hazard Location Class 1/Div 2
- CC2065PHL Rated Cooling: 982 Watts mounted to an uninsulated 24" x 24" x 16" Cabinet with 1GPM of water at 20°C, 40°C ambient air and 60°C cabinet air temperature (Temp Code T4)
- Designed for surface mounting on the outside of cabinet
- Housing is Stainless Steel (TYPE 316)
- Equipped with mounting gasket to maintain the TYPE 4X integrity of your cabinet
- Pressure tested to insure liquid tight seal
- Internal 6ft power cord
- Available with DC and AC (12VDC, 24VDC, 48VDC, 115VAC & 230VAC)
- Designation xxx indicates voltage
- Vertical mounting (as shown) only
- Coolant water pressure: Pressure tested to 100 psi. Safe working pressure is 60 psi.
- Recommended water flow rate (gallons per minute): 1GPM
DETAILS
Dimensions-Inches | ||||||||
---|---|---|---|---|---|---|---|---|
Model | Weight (lbs) | Rating (Watts) @ 20 °C ▲T | Rating (BTU/hr) @ 20 °C ▲T | Amps Current Draw at 115 V | Fan Size | Height | Width | Depth |
C2065PHL | 9 | 982 | 3,350 | 0.25 | 1 X 4" | 22.5 | 6.25 | 4.06 | 24.5 Watts /°C ∆T based on average internal cabinet temperature |
CERTIFICATIONS