CC3065
CC3065
- UL Listed for TYPE 4X environments, Hazard Location Class 1/ Div 2
- CC3065PHL Rated Cooling: 2,725 Watts mounted to an uninsulated 72" x 36" x 24" Cabinet with 1GPM of water at 20°C, 40°C ambient air and 60°C cabinet air temperature (Temp Code T4)
- Designed for surface mounting on the outside of cabinet
- Housing is Stainless Steel (TYPE 316)
- External water inlet and outlet connections
- Equipped with mounting gasket to maintain the TYPE 4X integrity of your cabinet
- Pressure tested to insure liquid tight seal
- Internal 6-ft power cord
- Available with DC and AC (12VDC, 48VDC, 115VAC & 230VAC) Designation xxx indicates voltage
- Vertical mounting (as shown) only
- Coolant water pressure: Pressure tested to 100 psi. Safe working pressure is 60 psi.
- Recommended water flow rate (gallons per minute): 1GPM
DETAILS
Dimensions-Inches | ||||||||
---|---|---|---|---|---|---|---|---|
Model | Weight (lbs) | Rating (Watts) @ 20 °C ▲T | Rating (BTU/hr) @ 20 °C ▲T | Amps Current Draw at 115 V | Fan Size | Height | Width | Depth |
CC3065PHL | 13 | 2,725 | 9,300 | 0.36 | 1 x 6" | 30 | 8.75 | 4.06 | 68.8 Watts /°C ∆T based on average internal cabinet temperature |
CERTIFICATIONS