CC2065

CC2065

  • UL Listed for TYPE 4X environments, Hazard Location Class 1/Div 2
  • CC2065PHL Rated Cooling: 982 Watts mounted to an uninsulated 24" x 24" x 16" Cabinet with 1GPM of water at 20°C, 40°C ambient air and 60°C cabinet air temperature (Temp Code T4)
  • Designed for surface mounting on the outside of cabinet
  • Housing is Stainless Steel (TYPE 316)
  • Equipped with mounting gasket to maintain the TYPE 4X integrity of your cabinet
  • Pressure tested to insure liquid tight seal
  • Internal 6ft power cord
  • Available with DC and AC (12VDC, 24VDC, 48VDC, 115VAC & 230VAC)
  • Designation xxx indicates voltage
  • Vertical mounting (as shown) only
  • Coolant water pressure: Pressure tested to 100 psi. Safe working pressure is 60 psi.
  • Recommended water flow rate (gallons per minute): 1GPM

DETAILS

Dimensions-Inches
Model Weight (lbs) Rating (Watts) @ 20 °C ▲T Rating (BTU/hr) @ 20 °C ▲T Amps Current Draw at 115 V Fan Size Height Width Depth
C2065PHL 9 982 3,350 0.25 1 X 4" 22.5 6.25 4.06
24.5 Watts /°C ∆T based on average internal cabinet temperature